BQKVQ - 21881 NICKEL CADMIUM STORAGE BATTERY

Product Identification

Product ID:21881 NICKEL CADMIUM STORAGE BATTERY
MSDS Date:03/05/1991
FSC:6140
NIIN:01-307-1326
MSDS Number: BQKVQ

Responsible Party
SAFT AMERICA INC PRIMARY BATTERY DIVISION
711-A INDUSTRIAL BLVD
VALDOSTA, GA 31603
US

Emergency Phone: 912-247-2331

Info Phone: 912-247-2331

Preparer: BETH LAS

Cage: 01306

Contractor
SAFT AMERICA INC PRIMARY BATTERY DIVISION
1886 VALDOSTA, GA 31601-6512 US

Telephone: 912-247-2331

Cage: 01306

Ingredients

CADMIUM (SARA III)

CAS: 7440-43-9

RTECS: EU9800000

Fraction By Weight: 7-13%

OSHA PEL SEE 1910.1027

ACGIH TLV: 0.01 MG/M3 DUST;9394

EPA Report Quantity: 10 LBS

DOT Report Quantity: 10 LBS


CADMIUM HYDROXIDE

Fraction By Weight: 7-13%

OSHA PEL 0.1 MG/M3 (CD FUME)

ACGIH TLV: 0.05 MG/M3 (CD FUME)


NICKEL (SARA III)

CAS: 7440-02-0

RTECS: QR5950000

Fraction By Weight: 23-30%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3; 9293


NICKEL HYDROXIDE (SARA III)

CAS: 12054-48-7

RTECS: QR7040000

Fraction By Weight: 23-30%

OSHA PEL 1 MG NI/M3

ACGIH TLV: 0.1 MG NI/M3; 9293

EPA Report Quantity: 10 LBS

DOT Report Quantity: 10 LBS


POTASSIUM HYDROXIDE (SARA III)

CAS: 1310-58-3

RTECS: TT2100000

Fraction By Weight: 4 - 8%

OSHA PEL C, 2 MG/M3

ACGIH TLV: C 2 MG/M3; 9293

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


COBALT HYDROXIDE

CAS: 21041-93-0

Fraction By Weight: 0.5%

OSHA PEL 0.05 MG/M3 (CO)

ACGIH TLV: 0.05 MG/M3 (CO)

Hazards

Routes of Entry: Inhalation:NO Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:NO
Health Hazards Acute and Chronic:ACUTE: UNDER NORMAL CONDITIONS OF USE,
NO EXPOSURE TO HAZARDOUS COMPONENTS EXISTS. ELECTROLYTE- SKIN & EYE
BURNS. IF INCINERATED, INHALATION OF FUME MAY CAUSE RESPIRATORY
SYSTEM IRRITATION TO PULMONAR Y EDEMA. CHRONIC: PROLONGED OR
REPEATEDEXPOSURE AY CAUSE KIDNEY DYSFUNCTION AND LUNG INJURY. ALSO
MAY CAUSE CANCER.
Explanation of Carcinogenicity:NICKEL AND CADMIUM ARE LISTED AS
POTENTIAL CARCINOGENS BY NTP, IARC, AND OSHA.
Effects of Overexposure:INHALED: COUGHING, WHEEZING, SHORTNESS OF
BREATH, FEVER, CHILLS. EYES: BURNING SENSATION, PAIN, REDNESS,
TEARING, BLURRED VISION. SKIN: PAIN, REDNESS, BLISTERS, BURNS,
SWELLING.
Medical Cond Aggravated by Exposure:IF INCINERATED: RESPIRATORY
DISORDERS, PROSTATE DISORDERS, LIVER AND KIDNEY DISORDERS.

First Aid

First Aid:EYES: FLUSH WITH LOTS OF WATER FOR 15 MINUTES, HOLD LIDS
OPEN. SEE DOCTOR. SKIN: REMOVE CONTAMINATED CLOTHES. FLUSH WITH
LOTS OF WATER. IF SYPTOMS PERSIST OR BURNED, SEE DOCTOR INHALED:
MOVE TO FRESH AIR. GET MEDICAL ATTENTION.

Fire Fighting

Flash Point:NONFLAMMABLE
Extinguishing Media:MEDIA APPROPRIATE FOR SURROUNDING FIRE.
Fire Fighting Procedures:WEAR SELF-CONTAINED BREATHING APPARATUS AND
FULL PROTECTIVE CLOTHING.
Unusual Fire/Explosion Hazard:TOXIC METAL FUMES MAY BE EVOLVED DURING
BURNING.

Accidental Release

Spill Release Procedures:IF ELECTROLYTE SPILLED, NEUTRALIZE WITH MILD
ACID THEN FLUSH WITH WATER.
Neutralizing Agent:5% ACETIC ACID

Handling

Handling and Storage Precautions:DO NOT BREAK OPEN BATTERY CASE. DO NOT
SHORT CIRCUIT. DO NOT INCINERATE.
Other Precautions:IF CASE BROKEN OPEN, ELECTROLYTE IS CORROSIVE. WEAR
PROPER PROTECTIVE CLOTHES/EQUIPMENT DURING CLEAN-UP.

Exposure Controls

Respiratory Protection:IF EMERGENCY CONDITIONS OCCUR; USE NIOSH/MSHA
APPROVED SCBA. USE IN ACCORDANCE WITH 29 CFR 1910.134.
Ventilation:NONE NORMALLY REQUIRED.
Protective Gloves:IF CASE BROKEN; USE RUBBER GLOVES.
Eye Protection:IF BROKEN; SAFETY GOGGLES.
Other Protective Equipment:IF INVOLVED IN FIRE, WEAR FULL PROTECTIVE
GEAR.
Work Hygienic Practices:WASH HANDS AFTER USE AND BEFORE EATING,
DRINKING, OR SMOKING. LAUNDER CONTAMINATED CLOTHES BEFORE REUSE.
Supplemental Safety and Health
AVOID CONTACT WITH INNER COMPONENTS.

Chemical Properties

HCC:B1
Appearance and Odor:OUTER METAL CASE CONTAINS PRISMATIC CELLS

Stability

Stability Indicator/Materials to Avoid:YES
NONE SPECIFIED BY MANUFACTURER.
Stability Condition to Avoid:NONE SPECIFIED BY MANUFACTURER.
Hazardous Decomposition Products:METAL OXIDE FUMES MAY BE EVOLVED AT
TEMPERATURES ABOVE MELTING POINT.

Disposal

Waste Disposal Methods:DISPOSE OF IN ACCORDANCE WITH LOCAL, STATE AND
FEDERAL REGULATIONS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.